Application
Fire detection and Fire alarm systems for Buildings, Public adress systems and Emergency lighting.
Fire performance
- Fire resistant: BS 6387 CWZ, BS 8434-2: 2003, BS EN 50200 PH 120.
- Fire retardant: BS EN 50266 1 & 2.1, IEC 60332 Part 3 & 1.
- Low smoke: BS EN 50268, IEC 61034.
- Halogen free: BS EN 50267, IEC 60754.
- Low toxicity: BS EN 50267, IEC 60754.
- Low corrosivity: BS EN 50267, IEC 60754.
Design
1. Conductor
- Bare copper:
- Solid class 1
2. Insulation
- Silicone rubber to BS 7655
3. Uninsulated protective conductor
- Tinned copper according to BS 6360 (same class and cross-sectional aera as insulated conductor)
4. Tape
- Aluminium/polyester tape with optional polyester tape
5. Outer sheath
- Halogen free polyolefin
- Colour: red
Marking
ALSECURE NX 200 PLUS - n x s -300/500V - BASEC - LPCB - BS 7629-1 - BS 6387 CWZ - BS 8434-2 - NEXANS - week/year - H
Core Identification
- 2 cores: brown - black
- 3 cores: brown - black - grey
- 4 cores: brown - black - grey - blue
|