Low voltage cables for fossil power plant

Description

Description

Standards

  • Product
    IEC 60228; IEC 60502-1
  • Test
    IEC 60332-3-22 Cat.A

Applications

These power and control cables are used for electricity supply in low voltage installation system for fossil power plant. When they are armoured, they are well adapted to underground use in industrial applications where mechanical protections are needed

 

Design

Conductor:

Solid (class 1) or stranded plain copper (class 2)

1 core: cross-sections from 25 to 630 mm²

2, 3, 4, 5G cores: cross-sections from 1.5 to 300 mm²

7, 10, 12, 14, 19, 24, 27, 30 and 37 cores: cross-sections 1.5 and 2.5 mm²

Insulation:

Cross-linked polyethylene (XLPE)

Inner covering:

None or

Polyvinyl chloride (PVC)

Armour:

None or

Galvanized steel wires (SWA) or aluminiums wires (AWA) or

Galvanized steel tapes (GSTA) or aluminium tapes (ATA)

Outer sheath:

Polyvinyl chloride (PVC)

 

Other conductor material, insulation material, type of armouring, sheath material, fire performances (iEC 60332-1, IEC 60332-3-24(C), IEC 60331) and cables with reduced neutral on request.

 

Core identification

1 core: black
2x to 5 G cores: according to HD308 S2
Above 5 cores:  black core printed with white number
 

 

Characteristics

Characteristics

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV

Usage characteristics

Usage characteristics

Fire retardant
EN IEC 60332-3-22 (cat A)
Oil resistance
Yes
Max. conductor temperature in service
90 °C
Operating temperature, range
-20 ... 60 °C

Resources

Resources

Documentation

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close