S740 (HN33-S-34) 14x4

Country ref. 01456810
GTIN 3427580036781
See all Remote control CERT cables S740 (HN 33-S-34) products
Description
Standards
International : HD 604 S1 ; IEC 60228National : HN 33-S-34; NF C 32-070/C1
Description
Application
These cables are used in transformer stations.They are protected against electro magnetic interferences.
Design
Conductor:
Stranded bare copper (class 2)
For 3x95+35 (3x95 : sector shape class 2 ; 35 : round shape class 2)
Insulation:
Polyvinyl chloride (PVC)
Assembling:
An inner sheath acting as a filler with pratically zero thickness
or assembling tape (optional)
Inner sheath:
Polyvinyl chloride (PVC)
Screen:
Corrugated copper tape
Outer sheath:
Polyvinyl chloride (PVC)
Colour : black
Marking
Cable standardized; Nber of cores & cross-section RTE S740 NEXANS 279 MM AAAA double marking + metric marking
Cable not standardized: Nber of cores & cross-section Type S740 (HN 33-S-34) NEXANS 279 MM AAAA double marking + metric marking
Core identification
Black core printed
Brown, yellow, green and light blue for:
3 x 50 + 25
3 x 95 + 35
Standards
Conform to the "Centre National d'Ingénierie Réseaux" (CNER) spécification and S740 (ex HN 33-S-34) nomenclature.
Characteristics
Construction characteristics | |
---|---|
Conductor material | Copper |
Insulation | PVC |
Inner sheath | PVC |
Screen | Corrugated copper screen |
Outer sheath | PVC |
Dimensional characteristics | |
Number of cores | 14 |
Conductor cross-section | 4mm² |
Minimum outer diameter | 26.6mm |
Maximum outer diameter | 29.3mm |
Approximate weight | 1201kg/km |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 0.6/1 kV |
Mechanical characteristics | |
Mechanical resistance to impacts | Medium |
Usage characteristics | |
Fire retardant | C1, NF C 32-070 |
Operating temperature, range | -20 .. 60°C |
Max. conductor temperature in service | 75°C |
Electro magnetic interference resistance | Yes |
Standard | Cable standardized |
Docs and info
Related links
Selling information
Minimum bending radius:
10 x outer diameter
To be doubled during laying operations