Description
- Armoured with galvanized steel wires (SWA) or aluminium wires (AWA)
- Oil resistant
Standards
International : IEC 60228; IEC 60332-3-22 Cat.A; IEC 60502-1Description
Applications
These power and control cables are used for electricity supply in low voltage installation system. They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plants...).
Design
Conductor:
Solid plain copper : 1.5 to 4 mm²
Stranded plain copper : 1.5 to 630 mm²
Insulation:
Cross-linked polyethylene (XLPE)
Bedding (optional):
Inner sheath acting as a filler with practically zero thickness or assembling polyester tape
Inner covering (inner sheath):
Polyvinyl chloride (PVC) Colour :black
Armour:
Galvanized steel wires (SWA) or aluminium wires (AWA) for 1 core cable
Outer sheath:
Polyvinyl chloride (PVC). Colour: black. Other colour on request.
Core identification
1 core: black
2x to 5G cores: according to HD 308 S2
Above 5 cores: black core printed with white number.
Marking
NEXANS 279 XLPE/PVC/AWA or SWA/PVC 0.6/1 kV Nber of cores and cross section Cu IEC 60332-3-22(A) MM YYYY manufacturing number + meter marking
Characteristics
Construction characteristics | |
---|---|
Conductor material | Plain copper |
Type of conductor | Stranded, Class 2 |
Insulation | XLPE (Cross-linked Polyethylene) |
Inner sheath | PVC |
Armour type | Aluminium Wire |
Outer sheath | PVC |
Protection | Yes |
With Green/Yellow core | No |
Dimensional characteristics | |
Number of cores | 1 |
Conductor cross-section | 630mm² |
Conductor diameter | 31.4mm |
Diameter over insulation | 36.2mm |
Diameter over inner sheath | 38.6mm |
Diameter over armour | 42.4mm |
Minimum outer diameter | 45.59mm |
Maximum outer diameter | 50.3mm |
Approximate weight | 7017.94kg/km |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 0.6/1 kV |
Mechanical characteristics | |
Mechanical resistance to impacts | Good |
Usage characteristics | |
Fire retardant | IEC 60332-3-22 |
Oil resistance | Yes |
Max. conductor temperature in service | 90°C |
Operating temperature, range | -20 .. 60°C |
Docs and info
Related documents
Selling information
Other fire performances IEC 60332-1 or IEC 60332-3 -24(C) and enhanced hydrocarbon resistance on request.
Minimum bending radius:
1 core: 10 x outer diameter
Multicores: 8 x outer diameter
To be doubled during laying operations
Cables with reduced neutral on request