Description
- Overall Screen (OS)
- With lead cover (LC)
- Aliphatic and aromatic hydrocarbons resistant
Standards
International : IEC 60332-3-22 Cat.ADescription
Applications
These compensation and extension cables are used with thermocouples for temperature measurements.They are well adapted to underground use in industrial applications, in moist areas, where chemical and mechanical protections are needed. The lead cover brings an enhanced resistance to aromatics hydrocarbons.
Design
Conductor:
Metal in accordance with the thermocouple, either solid cross section 0.5 mm² (1 x 0.8 mm), 1.34 mm² (1 x 1.30 mm) or flexible cross-section 1 mm² (14 x 0.30 mm)
Insulation:
Cross-linked polyethylene (XLPE)
Overall screen:
Binder tape
Tinned copper drain wire
Aluminium backed polyester tape
Bedding (inner sheath):
Polyvinyl chloride (PVC)
Colour : black or depends on thermocouple type
Lead cover
Bedding (intermediate sheath):
Polyvinyl chloride (PVC)
Colour : black or depends on thermocouple type
Armour:
Galvanized steel wires (SWA)
Outer sheath:
Polyvinyl chloride (PVC)
Colour: depends on thermocouple type
Core identification
See "identification sheet"
Marking
NEXANS 279 XLPE/OA.SCR/PVC/LC/PVC/SWA/PVC 170/300 V Nber of pairs & cross section Type of thermocouple IEC 60332-3-22(A) MM YYYY Manufacturing number + meter marking
Standards
EN 50288-7 (Design guide-lines)
HD 446.3 S1
Characteristics
Construction characteristics | |
---|---|
Insulation | XLPE (Cross-linked Polyethylene) |
Overall screen | Tinned copper drain wire + aluminium/polyester tape |
Inner sheath | PVC |
Lead Sheath | Yes |
Intermediate sheath | PVC |
Armour type | Galvanized steel wires |
Outer sheath | PVC |
Protection | Yes |
Dimensional characteristics | |
Conductor cross-section | 0.5mm² |
Number of pairs | 20 |
Conductor diameter | 0.8mm |
Diameter over insulation | 1.28mm |
Diameter over inner sheath | 14.5mm |
Lead cover diameter | 16.7mm |
Diameter over intermediate sheath | 18.7mm |
Diameter over armour | 21.2mm |
Minimum outer diameter | 23.9mm |
Maximum outer diameter | 26.3mm |
Approximate weight | 1377kg/km |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 170/300V |
Mechanical characteristics | |
Mechanical resistance to impacts | Good |
Usage characteristics | |
Fire retardant | IEC 60332-3-22 |
Chemical resistance | Aliphatic and aromatic hydrocarbons resistant |
Electro magnetic interference resistance | Yes |
Operating temperature, range | -20 .. 60°C |
Max. conductor temperature in service | 90°C |
Standard | EN |
Docs and info
* Thermocouple type
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
TC – Copper/copper nickel for copper/copper nickel thermocouple |
|
|
|
|
|
|
|
JC – Iron/copper nickel for iron/copper nickel thermocouple |
|
|
|
|
|
|
|
EC – Nickel chromium/copper nickel for nickel chromium/copper nickel thermocouple |
|
|
|
|
|
|
|
KC – Nickel chromium/nickel aluminium for nickel chromium/nickel aluminium thermocouple |
|
|
|
|
|
|
|
KCA – Iron/copper nickel for nickel chromium/nickel aluminium thermocouple |
|
|
|
|
|
|
|
KCB – Copper/copper nickel for nickel chromium/nickel aluminium thermocouple |
|
|
|
|
|
|
|
NC – Nickel chromium silicium/nickel silicium for nickel chromium silicium/nickel silicium thermocouple |
|
|
|
|
|
|
|
SC RC – Copper/copper nickel for platinium rhodium thermocouple |
|
|
|
|
|
|
|
BC – Copper/copper alloy for platinium rhodium/platinium rhodium thermocouple |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Selling information
Other fire performances IEC 60332-1 or IEC 60332-3-24(C) on request.
Minimum bending radius:
10 x outer diameter