Description
- Quality insurance according to RCC-E
- Zero halogen (SH)
- Control cables 0.3/0.5(0.6)kV
- Cables installed inside of the containment area (K1)
- Without Screen (SE)
- Unarmoured (NA)
Standards
International : IEC 60228; IEC 60332-3-23; IEC 60754-1; IEC 60754-2; IEC 61034-2National : NF C 32-070/C1
Description
Applications
These control cables allow connection to a variety of industrial equipement from control room.
Design
Conductor:
- Stranded (class 2) or flexible (class 5) plain copper
Insulation:
- Zero halogen (SH), cross-linked
Assembling:
- Polyester tape (optional)
Outer sheath:
- Low smoke, zero halogen (LSZH)
- Colour: Grey
Core identification
Black cores printed with white numbers
Optional: with G/Y core.
Marking
NEXANS 279 Nber of cores & cross-section Cu CST 74 C 068 K1 SH 0.3/0.5(0.6) kV YYYY Manufacturing number + metric marking
Characteristics
Construction characteristics | |
---|---|
Conductor material | Plain copper |
Type of conductor | Flexible, Classe 5 |
Insulation | Halogen-free |
Outer sheath | LSZH |
Halogen free | IEC 60754-1/IEC 60754-2 |
Dimensional characteristics | |
Conductor cross-section | 1.5mm² |
Number of cores | 7 |
Conductor diameter | 1.5mm |
Diameter over insulation | 2.7mm |
Minimum outer diameter | 10.9mm |
Maximum outer diameter | 12.5mm |
Approximate weight | 230kg/km |
Electrical characteristics | |
Rated Voltage Uo/U (Um) | 0.3/0.5(0.6)kV |
Usage characteristics | |
Operating temperature, range | -20 .. 60°C |
Fire retardant | NFC 32070 C1/IEC 60332-3-23(B) |
Life cycle 60years | Yes |
U.V resistance | Yes |
Radiation resistant | Yes |
Loss of coolant accident resistant | Yes |
Max. conductor temperature in service | 90°C |
Nuclear Classification | Class 1 E LOCA /K1 |
Docs and info
Theoretical characteristics
|
|
|||||||
NEXANS |
TYPICAL RESISTANCES |
REACTANCE |
SHORT-CIRCUIT CURRENT |
VOLTAGE |
IMPEDANCE |
CALORIFIC |
||
D.C. |
D.C. |
0,3 s max |
1 s max |
|||||
Ohms/Km |
Ohms/Km |
Ohms/Km |
kA |
kA |
V/A.Km |
Ohm |
MJ/m |
|
10266533 |
18,1 |
23,0 |
0,100 |
0,26 |
0,14 |
36,9 |
18,1 |
1.2 |
10266537 |
18,1 |
23,0 |
0,100 |
0,26 |
0,14 |
36,9 |
18,1 |
1.2 |
10263807 |
18,1 |
23,0 |
0,100 |
0,26 |
0,14 |
36,9 |
18,1 |
1.4 |
10263808 |
18,1 |
23,0 |
0,100 |
0,26 |
0,14 |
36,9 |
18,1 |
2.0 |
10265329 |
18,1 |
23,0 |
0,100 |
0,26 |
0,14 |
36,9 |
18,1 |
2.2 |
10272455 |
12,1 |
15,4 |
0,096 |
0,39 |
0,21 |
24,8 |
12,1 |
1.7 |
10272456 |
12,1 |
15,4 |
0,096 |
0,39 |
0,21 |
24,8 |
12,1 |
1.9 |
10236246 |
12,1 |
15,4 |
0,096 |
0,39 |
0,21 |
24,8 |
12,1 |
2.3 |
10261557 |
12,1 |
15,4 |
0,096 |
0,39 |
0,21 |
24,8 |
12,1 |
2.6 |
10272421 |
26,0 |
33,1 |
0,106 |
0,2 |
0,11 |
53,1 |
26 |
2.1 |
10237507 |
19,5 |
24,8 |
0,100 |
0,26 |
0,14 |
39,8 |
19,5 |
1.2 |
10272430 |
13,3 |
16,9 |
0.098 |
0,39 |
0,21 |
27,2 |
13,3 |
1.8 |
10272431 |
13,3 |
16,9 |
0.098 |
0,39 |
0,21 |
27,2 |
13,3 |
2.6 |
Selling information
Minimum bending radius:
10 x outer diameter
To be doubled during laying operations