Nexans H07VU 1x2,5 GREEN/YELLOW BOB 10m
Certifications and labels
Nexans H07VU 1x2,5 GREEN/YELLOW BOB 10m
H07V-U conductors are used for fixed protected installations : i.e. ligths or control gear (from offices, domestic or commercial buildings ...) with voltage ≤ 1000V AC or ≤ 750 V DC . ..
Read more- Nexans ref. : 10026523
- EAN : 3170238411071
Description
Description
Standards
-
ProductEN 50525-2-31; EN 50575; HD 21.3; IEC 60227-1; IEC 60228; NF C32-201/3
-
InstallationNF C15-100
-
TestIEC 60332-1-2
Application
Nexans H07V-U is intended for protected fixed electrical installations in dry locations for general power distribution circuits (excluding fire safety circuits), including:
- Residential buildings (single-family and multi-dwelling): final circuits for lighting, socket outlets, electric heating and ventilation systems (VMC), as well as wiring of distribution boards.
- Offices and commercial buildings: lighting and control circuits up to 1000 V AC or 750 V DC to earth.
Note
- For installations requiring enhanced fire performance, use H07Z1-U/R/K halogen-free conductors.
- For fire safety circuits (fire detection and alarm systems, emergency lighting, smoke extraction systems, etc.), use CR1-C1 cable.
Installation
Permitted laying options:
- In free air on insulating supports, in dry locations
- In mouldings, skirting trunking, conduits, ducts or cable trunking systems
- In conduits (surface-mounted or concealed in dry walls)
- Internal wiring of electrical panels, switchboards and enclosures
Not suitable for:
- Direct outdoor installation – PVC insulation is not resistant to UV radiation or weathering
- Damp, wet or flooded locations – moisture resistance limited to AD1 classification (protection against condensation only)
- Direct burial without additional mechanical protection
- Mobile applications or installations subject to repeated flexing – use H07V-K (Class 5) or H07Z-K instead
- Fire safety circuits (fire detection and alarm systems, emergency lighting, smoke extraction systems, etc.) – use CR1-C1 cable
Installation parameters
- Minimum installation temperature: -5 °C
- Minimum bending radius: 4 × overall diameter
Marking
S.Y + USE «har» H07V-U factory number
Range and colour Mobiway POP
Nexans MOBIWAY POP spool
Nexans MOBIWAY POP tool
Gammes et couleurs disponibles pour PASSEO
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Solid class 1
Conductor material
Bare copper
Conductor shape
Circular
Insulation
PVC
Lead free
Yes
Sheath colour
Green / Yellow
Dimensional characteristics
Dimensional characteristics
Approximate weight
- kg/km
Conductor cross-section
2.5 mm²
Maximum outer diameter
- mm
Number of cores
1
Electrical characteristics
Electrical characteristics
Rated Voltage Uo/U (Um)
450/750 V
Permissible current (one phase)
- A
Permissible current rating (3 conductors)
- A
Voltage drop, 3 conductors
- V/A.km
Voltage drop, single phase
- V/A.km
Mechanical characteristics
Mechanical characteristics
Mechanical resistance to impacts
Low
Maximum tensile strength
50 N/mm2
Usage characteristics
Usage characteristics
Max. conductor temperature in service
70 °C
Short-circuit max. conductor temperature
160 °C
Operating temperature, range
-5 ... 70 °C
Minimum installation temperature
5 °C
Weather resistance
No
Chemical resistance
Accidental
Water proof
Low
Bending factor when laying
4 (xD)
Length
10 m
Packaging
-
Fire safety characteristics
Fire safety characteristics
Flame retardant
EN 60332-1-2
Resources
Resources
Documentation
Licence H07V-U
pdf — 66.3 kB
CMC PASSEO VU
pdf — 250.3 kB
CMC H07V-U
pdf — 237.3 kB
Brochure gamme 2024
pdf — 3.1 MB
FLYER MOBIWAY POP
pdf — 884.8 kB
Declaration of Performance
- Declaration of Performance n° : 1000230-FRLV
- Certification Date : 10/11/17
- AVCP (Assessment and Verification of Constancy of Performance) : System 3
- Notified body : 1812
- Declared performance : Eca
Dealer locator
Waiting…
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania