NEXANS H07ZZ-F 1x35 PROTECT Cca-s1a, d2, a1

Description

Description

Standards

  • Product
    EN 50525-3-21; EN 50575; IEC 60228

Advantages

Nexans H07ZZ-F PROTECT cables, available as single-core conductors from 35 to 630 mm2, have been designed to be flame non-propagating, halogen-free, and to emit low smoke in the event of a fire. The gases released are neither acidic nor corrosive. Thanks to their excellent fire performance (minimum Cca-s1a, d2, a1), they are particularly suited to critical buildings such as ERP and IGH. They can also be used in workplace buildings (ERT) or in residential buildings.

Nexans H07ZZ-F PROTECT cables contain 10% recycled copper, reducing their carbon footprint. Nexans provides all environmental data for its products (PEP Ecopassport).

 

The advantages of this range are:

  • Very good fire resistance, flame non-propagating, and halogen-free
  • 35 mm2 to 70 mm2: Cca-s1a, d2, a1
  • 95 mm2 to 630 mm2: B2ca-s1a, d2, a1
  • Manufactured in France at our Bohain plant
  • 10% recycled copper

Installation

Nexans H07ZZ-F PROTECT cables can be installed on cable trays, on racks, inside cable ducts, or fixed to walls, outdoors with or without protection. They can also be buried with additional mechanical protection, or without protection thanks to their good UV resistance.

Maximum continuous operating temperature of the conductor under normal conditions:

  • +60°C (in all mobile installation cases)
  • +90°C (fixed and protected installation)
  • +250°C (in case of short circuit)

The current-carrying capacity is measured for an ambient temperature of 30°C and a maximum conductor operating temperature of 90°C, in accordance with IEE Table 4F2A.
For other temperatures, please refer to the correction factors.

 

CONSTRUCTION

Conductor : Electrolytic copper, class 5 (flexible), in accordance with EN 60228 and IEC 60228.

Insulation : Halogen-free thermosetting rubber, type EI8 according to EN 50363-5.

Outer sheath : Halogen-free flexible thermosetting rubber, type EM8 according to EN 50363-6.
Black colour.

 

​Minimum bending radius

  • Dynamic: 6 to 8 x the overall diameter of the cable.
  • Static: 3 x the overall diameter of the cable if the diameter is under or equal to 12 mm; 4 x if the overall diameter is over 12 mm.

 

Pulling force on cable conductors

When pulling cables, all conductors must share the mechanical load equally. The pulling force must under no circumstances exceed 15 N/mm2 of overall cross-section.

However, the maximum pulling force must never exceed 1000 N in total, even if the above rule could lead to higher values for large cable cross-sections.

 

Marking

Nexans H07ZZ-F 1X Protect 213 USE HAR + CPR + marking

Our range

Comportement au feu Cca-S1a, d2, a1 :

10171274 NEXANS H07ZZ-F 1x35 PROTECT Cca-s1a, d2, a1

10286785 NEXANS H07ZZ-F 1x50 PROTECT Cca-s1a, d2, a1

10286786 NEXANS H07ZZ-F 1x70 PROTECT Cca-s1a, d2, a1

 

 

Comportement au feu B2ca-S1a, d2, a1 :

10056440 NEXANS H07ZZ-F 1x95 PROTECT B2ca-s1a, d2, a1

10056852 NEXANS H07ZZ-F 1x120 PROTECT B2ca-s1a, d2, a1

10056660 NEXANS H07ZZ-F 1x150 PROTECT B2ca-s1a, d2, a1

10056441 NEXANS H07ZZ-F 1x185 PROTECT B2ca-s1a, d2, a1

10056442 NEXANS H07ZZ-F 1x240 PROTECT B2ca-s1a, d2, a1

10069724 NEXANS H07ZZ-F 1x300 PROTECT B2ca-s1a, d2, a1

10286565 NEXANS H07ZZ-F 1X400 PROTECT B2ca-s1a, d2, a1

10287536 NEXANS H07ZZ-F 1X500 PROTECT B2ca-s1a, d2, a1

10285245 NEXANS H07ZZ-F 1X630 PROTECT B2ca-s1a, d2, a1

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Bare copper
Conductor flexibility
Flexible class 5
Insulation
Special cross-linked elastomer
Outer sheath
Special cross-linked elastomer
Sheath colour
Black
Lead free
Yes
With Green/Yellow core
No
Conductor shape
Circular
With smaller neutral conductor
No

Dimensional characteristics

Dimensional characteristics

Number of cores
1
Conductor cross-section
35 mm²
Maximum outer diameter
17.9 mm
Minimum outer diameter
14.3 mm
Approximate weight
482 kg/km
Neutral conductor section (when smaller)
- mm²

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
450/750 V
Permissible current rating in open air
169 A
Voltage drop, single phase
1.04 V/A.km
Permissible mobile installation current
120 A

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Very good
Cable flexibility
Flexible

Usage characteristics

Usage characteristics

Packaging
Cut to length
Length
- m
Chemical resistance
Accidental
Water proof
Good
Flame retardant
IEC 60322-1-2; IEC 60332-3-24
Max. conductor temperature in service
90 °C
Minimum dynamic operating bending radius
107.4 mm
Minimum static operating bending radius
- mm
Oil resistance
Yes
Operating temperature, range
-25 ... 55 °C
Short-circuit max. conductor temperature
250 °C
Weather resistance
Yes

Resources

Resources

Declaration of Performance

  • Declaration of Performance n° : 1001348-FRBH
  • Certification Date : 9/8/25
  • AVCP (Assessment and Verification of Constancy of Performance) : System 1+
  • Notified body : 2661
  • Declared performance : Cca-s1a,d2,a1

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close