J3UR 3
J3UR 3
Medium voltage transition joints (synthetic to paper)
Up to 24kV
- Nexans ref. : 8796
- Country ref. : 01008796
Description
Description
Standards
- 
                                            ProductNF C33-001
Use
Joint between :
- 3 single core synthetic insulated MV cables
- 3 single core synthetic insulated MV cables and 3 single core paper insulated MV cables
- 3 single core paper insulated MV cables.
Cable specifications :
- UTE C 33-223
- NF C 33-220 (HN 33-S-22)
- NF C 33-223 (HN 33-S-23)
- NF C 33-100
- Section : from 50 to 240 mm².
Standards
Meets the NF C 33-001 test standard.
Conditioning
Each conditioning contains the necessary to make a three core joint as well as detailled fitting instructions.
Accessories
The connection bushings (type RJ) are to be supplied separately (see Connections for joints/branch joints.
For the resin injection in case of a pump injection, use an injection tool (see Accessories for joints/branch joints).
Characteristics
Characteristics
Construction characteristics
Construction characteristics
                                                                Technology
                                                            
                                                            
                                                                Wrapped 
                                                            
                                                        
                                                                Conductor material
                                                            
                                                            
                                                                Copper or Aluminum 
                                                            
                                                        Dimensional characteristics
Dimensional characteristics
                                                                Conductor cross-section, range
                                                            
                                                            
                                                                95 ... 240 mm²
                                                            
                                                        Electrical characteristics
Electrical characteristics
                                                                Rated Voltage Uo/U (Um)
                                                            
                                                            
                                                                12 / 20 (24) kV 
                                                            
                                                        
                                                                Dielectric withstand voltage, 50Hz 1mn
                                                            
                                                            
                                                                55 kV
                                                            
                                                        
                                                                Impulse voltage
                                                            
                                                            
                                                                125 kV
                                                            
                                                        Usage characteristics
Usage characteristics
                                                                Ambient installation temperature, range
                                                            
                                                            
                                                                5 ... 40 °C
                                                            