EN 50288-7 XLPE Insulation OS Unarmoured 30x2x1,5

Description

Description

Standards

  • International
    IEC 60332-3-22 Cat.A

Applications

These instrumentation and communication cable are used to transmit analogue or digital signals in measurement and process control where chemicals may be present. 

 

Design

Conductor:

Stranded bare copper class 2

Insulation:

Cross-linked polyethylene (XLPE)

Overall screen

Polyester tape

Tinned copper drain wire 

Aluminium backed polyester tape

Outer sheath:

Polyvinyl chloride (PVC). 

Colour: black. 

Other colour on request. 

 

Core identification

Pair: white - black
Quad:  white - black - red - blue (2 pair cables assembled as a quad)
White core printed with pair number
 

Marking

NEXANS 279 XLPE/OA.SCR/PVC 170/300V Nber of pairs & cross-section Cu IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking

 

Standards

EN 50288-7 (Design guide-lines)

 

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Bare copper
Type of conductor
Stranded, class 2
Insulation
XLPE (Cross-linked Polyethylene)
Overall screen
Tinned copper drain wire + aluminium/polyester tape
Outer sheath
PVC
Protection
no

Dimensional characteristics

Dimensional characteristics

Number of pairs
30
Conductor cross-section
1.5 mm²
Diameter over insulation
2.16 mm
Approximate weight
1237 kg/km
Conductor diameter
1.5 mm
Maximum outer diameter
30.8 mm
Minimum outer diameter
27.9 mm

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
170/300V

Usage characteristics

Usage characteristics

Fire retardant
IEC 60332-3-22
Oil resistance
Yes
Electro magnetic interference resistance
Yes
Operating temperature, range
-20 ... 60 °C
Max. conductor temperature in service
90 °C
Standard
EN

Resources

Resources

Documentation

Selling & delivery Information


Other fire performances IEC 60332-1 or IEC 60332-3-24(C) and enhanced hydrocarbon resistance on request.


Minimum bending radius:

10 x outer diameter
To be doubled during laying operations


Tinned copper conductors available on request

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close