EN 50288-7 Hypron® XLPE Insulation OS Armoured 5x2x1,34

Description

Description

Standards

  • International
    IEC 60332-3-22 Cat.A

Applications

These compensation and extension cables are used with thermocouple for temperature measurements in moist areas and where aliphatic and aromatic hydrocarbons may be present. They are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plant...). Hypron® offers an alternative to conventional lead sheathed cable and is an environmental friendly solution.

 

Design

Conductor:

Metal in accordance with the thermocouple, either solid cross section 0.5 mm² (1 x 0.8 mm), 1.34 mm² (1 x 1.30 mm) or flexible cross-section 1 mm² (14 x 0.30 mm)

Insulation:

Cross-linked polyethylene (XLPE)

Binder tape

Bedding

Inner sheath:

Polyvinyl chloride (PVC)

Colour: black

Overall screen/sealing barrier

Tinned copper drain wire 

Aluminium/polyethylene tape

Bedding:

High density polyethylene (PE)

Colour: black

Special sheath (intermediate sheath):

Polyamide

Armour:

Galvanized steel wires (SWA)

Outer sheath:

Polyvinyl chloride (PVC)

Colour: depends on thermocouple type

 

Core identification

See identification sheet

 

Marking

NEXANS 279 XLPE/PVC/AL/HDPE/NC/SWA/PVC 170/300V Nber of pairs & cross-section type of thermocouple IEC 60332-3-22(A) MM YYYY Manufacturing number + metric marking

 

Standards

EN 50288-7 (Design guide-lines)

HD 446.3 S1

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Insulation
XLPE (Cross-linked Polyethylene)
Inner sheath
PVC
Overall screen
Tinned copper drain wire + aluminium/polyethylene tape
Material of bedding
High-density polyethylene (PE)
Intermediate sheath
Polyamide
Armour type
Galvanized steel wires
Outer sheath
PVC
Lead free
Yes
Protection
Yes

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
1.34 mm²
Number of pairs
5
Conductor diameter
1.3 mm
Diameter over insulation
1.78 mm
Diameter over inner sheath
11.5 mm
Diameter over intermediate sheath
14.8 mm
Diameter over armour
16.6 mm
Minimum outer diameter
21.9 mm
Maximum outer diameter
24.2 mm
Approximate weight
910 kg/km

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
170/300V

Mechanical characteristics

Mechanical characteristics

Mechanical resistance to impacts
Good

Usage characteristics

Usage characteristics

Fire retardant
IEC 60332-3-22
Chemical resistance
Aliphatic and aromatic hydrocarbons resistant
Electro magnetic interference resistance
Yes
Operating temperature, range
-20 ... 60 °C
Max. conductor temperature in service
90 °C
Standard
EN

Resources

Resources

Documentation

Selling & delivery Information


Other fire performances IEC 60332-1 or IEC 60332-3-24(C) on request.


Minimum bending radius:

15 x outer diameter
To be doubled during laying operations


Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close