74C068 SH C 500V 3x1.5 Cu2 K1 SE NA

Description

Description

Standards

  • International
    IEC 60228; IEC 60332-3-23; IEC 60754-1; IEC 60754-2; IEC 61034-2
  • National
    NF C32-070/C1; NF C32-070/C1

Applications

These control cables allow connection to a variety of industrial equipement from control room.

Design

Conductor:
- Stranded (class 2) or flexible (class 5) plain copper
Insulation:
- Zero halogen (SH), cross-linked
Assembling:
- Polyester tape (optional)
Outer sheath:
- Low smoke, zero halogen (LSZH)
- Colour: Grey

Core identification

Black cores printed with white numbers
Optional: with G/Y core.

Marking

NEXANS 279  Nber of cores & cross-section Cu CST 74 C 068  K1 SH 0.3/0.5(0.6) kV YYYY  Manufacturing number  + metric marking

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Conductor material
Plain copper
Type of conductor
Stranded, class 2
Insulation
Halogen-free
Outer sheath
LSZH
Halogen free
IEC 60754-1; IEC 60754-2

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
1.5 mm²
Number of cores
3
Conductor diameter
1.5 mm
Diameter over insulation
2.7 mm
Minimum outer diameter
8.8 mm
Maximum outer diameter
10.1 mm
Approximate weight
140 kg/km

Electrical characteristics

Electrical characteristics

Max. DC resistance of the conductor at 20°C
12.1 Ohm/km
Maximum DC resistance of the conductor at 90°C
15.400 Ohm/km
Reactance at 50 Hz
0.096 Ohm/km
Short Circuit Current 0,3 s Max
0.39 kA
Short Circuit Current 1 s Max
0.21 kA
Voltage Drop
24.8 V/A.km
Impedance at 50 Hz
12.1 Ohm
Calorific Power
1.7 MJ/m
Rated Voltage Uo/U (Um)
0.3/0.5(0.6)kV

Usage characteristics

Usage characteristics

Operating temperature, range
-20 ... 60 °C
Smoke density
IEC 61034-2
Fire retardant
NF C 32070 C1; IEC 60332-3-23
Life cycle 60years
Yes
U.V resistance
Yes
Radiation resistant
Yes
Loss of coolant accident resistant
Yes
Max. conductor temperature in service
90 °C
Nuclear Classification
Class 1 E LOCA /K1

Resources

Resources

Documentation

xlsx — 0 B

Selling & delivery Information

Minimum bending radius:

10 x outer diameter
To be doubled during laying operations

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close