H1-XDV-AS 3x150 +70

Description

Description

Standards

  • National
    NF C33-210

Application

Low voltage buried cables with standard NF C33-210 for distribution public networks, three conductors + neutral.

Characteristics

The phase conductors are made of solid or stranded circular (class 2) aluminum depending on type.

The neutral conductor made of Core : aluminum stranded circular (class 2) of solid round and sheathed with lead.

The watertightness between the lead sheath is made with a waterproof material.

Conductors laid up/Filling

The phase conductors and neutral are assembled in a way, which makes them easy to separate to splice with branching wires.

Over phase and neutral conductors, a galvanized steel armour wound in direct the lead sheath. This construction is then sheathed PVC, with high mechanical properties.

Filler PVC material only 50 mm2.

Electrical characteristics

  • Rated Voltage : 0.6/1 kV.
  • Test Voltage : 3.5 kV for 15 minutes.
  • Resistance of the sheath to voltage surges : 1.2/50 µs with positive or negative polarity and a peak value of 20 kV.

Marking

H1 XDV-AS  "section"  DISTRICABLE ® 211 NF C33-210 «Manufactured number / manufactured year / metric marks/ manufactured date. »

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Outer sheath
PVC
Conductor material
Aluminum
Armour type
-
Conductor flexibility
Stranded class 2
Conductor shape
Sector-shaped
Insulation
XLPE (chemical)
Material of filler / inner sheath
-
Protection
Watertight textile material
Screen
Two semi-lapped galvanized mild steel tapes
Sheath colour
Black

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
150 mm²
Approximate weight
2570 kg/km
Maximum outer diameter
48.5 mm
Minimum outer diameter
36.5 mm
Neutral conductor section (when smaller)
70 mm²
Number of cores
4
Number of phases
3

Electrical characteristics

Electrical characteristics

Max. linear resistance, phase conductor
0.206 Ohm/km
Permissible current rating in open air
324 A
Permissible current rating when buried
300 A
Rated Voltage Uo/U (Um)
0.6/ 1 (1.2) kV
Resistance of neutral conductor at 20ºC
0.443 Ohm/km
Voltage drop, 3 conductors
0.51 V/A.km

Usage characteristics

Usage characteristics

Length
- m
Packaging
Cut to length
Flame retardant
C2, NF C 32-070
Minimum static operating bending radius
390 mm
Resistant to termites
No

Resources

Resources

Documentation

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*