FR-N1XD9-AR 3x35 +54.6 +16 NF C33-209

Description

Description

Standards

  • Product
    HD 626; NF C32-013; NF C33-209
  • International
    IEC 60298
  • National
    NF C11-201

Application

NF C33-209 Network distribution bundled conductors with neutral messenger are designed for rural and urban areas.

Some important cable characteristics are :

  • Ultraviolet radiation resistance,
  • Ozone resistance,
  • High dielectric strength,
  • Light and easy to handle.

Installation

The NF C11-201 standard´s procedures determine the installation procedures for low voltage overhead lines.

These cables are NOT ALLOWED to be buried, even in conduits.

Description

The bundled conductor cables have aluminum conductors, insulated with XLPE, they have good durability and thermal resistance.

Messenger caracteristics

  • core : circular stranded in AGS aluminum alloy, cross-section area 54.6 mm²
  • Insulation : Black XLPE
  • nominal cross section : 54.6 mm²
  • core diameter : 9.2 mm to 9.6 mm
  • insulated core diameter : min. 12.3 mm, max. 13.0 mm
  • min. breaking load : 1660 daN

Marking

  • Neutral :

211 NF C33-209 211 « manufacturing number », « metric marks » ink printed.

  • Phase 1, 2, 3 :

the identification number is printed and embossed on insulation.

  • Public lighting:

«EP1», «EP2 » is printed and embossed on each conductor, «EP3» if three conductors are required.

Electrical characteristics

  • Rated voltage : 0.6/1 kV
  • Test voltage : 4 kV AC
  • Resistance to voltage surges : 1.2/50µs with a positive or negative polarity and a peak value of 20 kV.

Low carbon offer

Low carbon at a glance

Characteristics

Characteristics

Construction characteristics

Construction characteristics

Public lighting
1 x 16 mm²
Colour
Black
Conductor flexibility
Stranded class 2
Conductor material
Aluminum
Conductor shape
Circular
Insulation
XLPE
Neutral messenger
AAAC - All Alloy Aluminium Conductor

Dimensional characteristics

Dimensional characteristics

Conductor cross-section
35 mm²
Number of cores
3

Electrical characteristics

Electrical characteristics

Rated Voltage Uo/U (Um)
0,6/1 kV

Usage characteristics

Usage characteristics

Packaging
Cut to length

Resources

Resources

Documentation

Selling & delivery Information

Marking

  • Neutral :

211 NF C33-209 211 « manufacturing number », « metric marks » ink printed.

  • Phase 1, 2, 3 :

the identification number is printed and embossed on insulation.

  • Public lighting:

«EP1», «EP2 » is printed and embossed on each conductor, «EP3» if three conductors are required.

Contact us

Topics on which you wish to get more informations:

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close

Contact us

Required fields*

Please check your entry and try again.

An email address must contain a single @

Personal data protector

You have the right to object to the processing of your personal data and/or their use for direct marketing or commercial purposes

Thank you!

Thanks for contacting us. We will be in touch with you shortly.

Error

An error occurred. Please try again.

Close